Circuit Breaker Test Sheet
Project Information
form id= "frm-swbd-proj-info"
Name Plate Data new
form id= "frm-lv-cb-nameplate"
SETTINGS
Basic form layout
Visual and Mechanical Inspection
Basic form layout
TEST DATA
Protective Functions
Ground Fault Protection:
Contact Resistance Test
Measurement should be taken across open contacts (line-load)
NETA ATS: Microhm or dc millivolt drop values shall not exceed the high levels of the normal range as indicated in the manufacturer’s published data. If manufacturer’s published data is not available, investigate values that deviate from adjacent poles or similar breakers by more than 50 percent of the lowest value.
Insulation Resistance Test
NETA ATS: Perform insulation-resistance tests for one minute on each pole, phase-to-phase, phase-to-ground, and phase-to-Neutral with the circuit breaker closed, and across each open pole. Apply voltage in accordance with manufacturer’s published data. In the absence of manufacturer’s published data, use Table 100.1.
Project Information
Name Plate Data
Basic form layout
TEST DATA
Protective Funnctions