NETA ATS
Circuit Breakers
NETA ATS
7.6.1.3 Circuit
Breakers, Air, Medium-Voltage
A. Visual and Mechanical
Inspection:
- Compare equipment nameplate data with drawings and specifications
- Inspect physical and mechanical condition.
- Inspect anchorage, alignment, and grounding.
- Verify that all maintenance devices are available for servicing and operating the breaker.
- Verify the unit is clean.
- Verify the arc chutes are intact.
- Inspect moving and stationary contacts for condition and alignment.
- If recommended by manufacturer, slow close/open breaker and check for binding, friction,
contact alignment, and penetration. Verify that contact sequence is in accordance with
manufacturer’s published data. In the absence of manufacturer’s published data, refer to
ANSI/IEEE C37.04.
- Perform all mechanical operation tests on the operating mechanism in accordance with
manufacturer’s published data.
- Inspect bolted electrical connections for high resistance using one or more of the following
methods:
- Use of a low-resistance ohmmeter in accordance with Section 7.6.1.3.B.1.
- Verify tightness of accessible bolted electrical connections by calibrated torquewrench
method in accordance with manufacturer’s published data or Table 100.12.
- Perform a thermographic survey in accordance with Section 9.
- verify cell fit and element alignment.
- Verify racking mechanism operation.
- Inspect puffer operation.
- Verify appropriate lubrication on moving current-carrying parts and on moving and sliding
surfaces.
- Perform contact-timing test.
- *Perform mechanism-motion analysis.
- *Perform trip/close coil current signature analysis.
- Record as-found and as-left operation-counter readings.
B. Electrical Tests:
- Perform resistance measurements through bolted connections with a low-resistance
ohmmeter, if applicable. See Section 7.6.1.3.A.10.1.
- Perform insulation-resistance tests for one minute on each pole, phase-to-phase and phase-toground
with circuit breaker closed, and across each open pole. Apply voltage in accordance
with manufacturer’s published data. In the absence of manufacturer’s published data, use
Table 100.1.
- Perform a contact/pole-resistance test.
- *Perform insulation-resistance tests on all control wiring with respect to ground. Applied
potential shall be 500 volts dc for 300-volt rated cable and 1000 volts dc for 600-volt rated
cable. Test duration shall be one minute. For units with solid-state components or control
devices that can not tolerate the applied voltage, follow manufacturer’s recommendation.
- With breaker in the test position, make the following tests:
- Trip and close breaker with the control switch.
- Trip breaker by operating each of its protective relays.
- Verify mechanism charge, trip-free, and antipump functions.
- Perform minimum pickup voltage tests on trip and close coils in accordance with
manufacturer’s published data.
- *Perform power-factor or dissipation-factor tests with breaker in both the open and closed
positions.
- *Perform power-factor or dissipation-factor tests on each bushing equipped with a powerfactor/
capacitance tap. In the absence of a power-factor/ capacitance tap, perform hot-collar
tests. These tests shall be in accordance with the test equipment manufacturer’s published
data.
- Perform a dielectric withstand voltage test on each phase with the circuit breaker closed and
the poles not under test grounded. Apply voltage in accordance with manufacturer’s
published data. In the absence of manufacturer’s published data, use Table 100.19.
- Measure blowout coil circuit resistance.
- Verify operation of heaters.
- Test instrument transformers in accordance with Section 7.10.
C. Test Values – Visual and
Mechanical
- Mechanical operation and contact alignment shall be in accordance with manufacturer’s
published data. (7.6.1.3.A.9)
- Compare bolted connection resistance values to values of similar connections. Investigate
values which deviate from those of similar bolted connections by more than 50 percent of the
lowest value. (7.6.1.3.A.10.1)
- Bolt-torque levels shall be in accordance with manufacturer’s published data. In the absence
of manufacturer’s published data, use Table 100.12. (7.6.1.3.A.10.2)
- Results of the thermographic survey shall be in accordance with Section 9. (7.6.1.3.A.10.3)
- Contact timing values shall be in accordance with manufacturer’s published data.
(7.6.1.3.A.15).
- Travel and velocity values shall be in accordance with manufacturer’s published data.
(7.6.1.3.A.16)
- Trip/close coil current values shall be in accordance with manufacturer’s published data.
(7.6.1.3.A.17).
- Operations counter shall advance one digit per close-open cycle. (7.6.1.3.A.18)
D. Test Values – Electrical
- Compare bolted connection resistance values to values of similar connections. Investigate
values which deviate from those of similar bolted connections by more than 50 percent of the
lowest value.
- Insulation-resistance values of circuit breakers shall be in accordance with manufacturer’s
published data. In the absence of manufacturer’s published data, use Table 100.1. Values of
insulation resistance less than this table or manufacturer’s recommendations should be
investigated.
- Microhm or dc millivolt drop values shall not exceed the high levels of the normal range as
indicated in the manufacturer’s published data. In the absence of manufacturer’s published
data, investigate values that deviate from adjacent poles or similar breakers by more than 50
percent of the lowest value.
- Insulation-resistance values of control wiring shall not be less than two megohms.
- Breaker mechanism charge, close, open, trip, trip-free, and antipump features shall function
as designed.
- Minimum pickup voltage of the trip and close coils shall conform to the manufacturer’s
published data. In the absence of the manufacturer’s published data, refer to Table 100.20.
- Power-factor or dissipation-factor values shall be compared with previous test results of
similar breakers or manufacturer’s published data.
- Power-factor or dissipation-factor and capacitance values shall be within ten percent of
nameplate rating for bushings. Hot collar tests are evaluated on a milliampere/milliwatt loss
basis, and the results shall be compared to values of similar bushings.
- If no evidence of distress or insulation failure is observed by the end of the total time of
voltage application during the dielectric withstand test, the circuit breaker is considered to
have passed the test.
- The blowout coil circuit shall exhibit continuity.
- Heaters shall be operational.
- The results of instrument transformer tests shall be in accordance with Section 7.10.
NETA ATS
7.6.3 Circuit
Breakers, Vacuum, Medium-Voltage
A. Visual and Mechanical
Inspection:
- Compare equipment nameplate data with drawings and specifications.
- Inspect physical and mechanical condition.
- Inspect anchorage, alignment, and grounding.
- Verify that all maintenance devices such as special tools and gauges specified by the
manufacturer are available for servicing and operating the breaker.
- Verify the unit is clean.
- Perform all mechanical operation tests on the operating mechanism in accordance with
manufacturer’s published data.
- Measure critical distances such as contact gap as recommended by manufacturer.
- Inspect bolted electrical connections for high resistance using one or more of the following
methods:
- Use of low-resistance ohmmeter in accordance with Section 7.6.3.B.1.
- Verify tightness of accessible bolted electrical connections by calibrated torquewrench
method in accordance with manufacturer’s published data or Table 100.12.
- Perform thermographic survey in accordance with Section 9.
- Verify cell fit and element alignment.
- Verify racking mechanism operation.
- Verify appropriate lubrication on moving, current-carrying parts and on moving and sliding
surfaces.
- Perform contact-timing test.
- *Perform trip/close coil current signature analysis.
- *Perform mechanism motion analysis.
- Record as-found and as-left operation counter readings.
B. Electrical Tests:
- Perform resistance measurements through bolted connections with a low-resistance
ohmmeter, if applicable, in accordance with Section 7.6.3.A.8.1.
- Perform insulation-resistance tests for one minute on each pole, phase-to-phase and phase-toground
with the circuit breaker closed, and across each open pole. Test voltage shall be in
accordance with manufacturer’s published data. In the absence of manufacturer’s published
data, use Table 100.1.
- *Perform insulation-resistance tests on all control wiring with respect to ground. Applied
potential shall be 500 volts dc for 300-volt rated cable and 1000 volts dc for 600-volt rated
cable. Test duration shall be one minute. For units with solid-state components, follow
manufacturer’s recommendation.
- *Perform dynamic contact/pole resistance test.
- Perform minimum pickup voltage tests on trip and close coils in accordance with
manufacturer’s published data.
- Verify correct operation of any auxiliary features such as electrical close and trip operation,
trip-free, and antipump function.
- Trip circuit breaker by operation of each protective device. Reset all trip logs and indicators.
- *Perform power-factor or dissipation-factor tests on each pole with the breaker open and each
phase with the breaker closed.
- *Perform power-factor or dissipation-factor tests on each bushing equipped with a powerfactor/
capacitance tap. In the absence of a power-factor/ capacitance tap, perform hot-collar
tests. These tests shall be in accordance with the test equipment manufacturer’s published
data.
- *Perform magnetron atmospheric condition (MAC) test on each vacuum interrupter.
- Perform vacuum bottle integrity (dielectric withstand voltage) test across each vacuum bottle
with the breaker in the open position in strict accordance with manufacturer’s published data.
- Perform a dielectric withstand voltage test in accordance with manufacturer’s published data.
- Verify operation of heaters.
- Test instrument transformers in accordance with Section 7.10.
C. Test Values – Visual and
Mechanical
- Critical distance measurements such as contact gap shall be in accordance with the
manufacturer’s published data. (7.6.3.A.7)
- Compare bolted connection resistance values to values of similar connections. Investigate
values which deviate from those of similar bolted connections by more than 50 percent of the
lowest value. (7.6.3.A.8.1)
- Bolt-torque levels shall be in accordance with manufacturer’s published data. In the absence
of manufacturer’s published data, use Table 100.12. (7.6.3.A.8.2)
- Results of the thermographic survey shall be in accordance with Section 9. (7.6.3.A.8.3)
- Contact timing values shall be in accordance with manufacturer’s published data.
(7.6.3.A.12)
- Trip/close coil current values shall be in accordance with manufacturer’s published data.
(7.6.3.A.13)
- Travel and velocity values shall be in accordance with manufacturer’s published data.
(7.6.3.A.14)
- Operation counter shall advance one digit per close-open cycle. (7.6.3.A.15)
-
D. Test Values – Electrical
<
- Compare bolted connection resistance values to values of similar connections. Investigate
values which deviate from those of similar bolted connections by more than 50 percent of the
lowest value.
- Insulation-resistance values of circuit breakers shall be in accordance with manufacturer’s
published data. In the absence of manufacturer’s published data, use Table 100.1. Values of
insulation resistance less than this table or manufacturer’s recommendations should be
investigated.
- Insulation-resistance values of control wiring shall not be less than two megohms.
- Microhm or dc millivolt drop values shall not exceed the high levels of the normal range as
indicated in the manufacturer’s published data. In the absence of manufacturer’s published
data, investigate values that deviate from adjacent poles or similar breakers by more than 50
percent of the lowest value.
- Dynamic contact resistance values shall be in accordance with manufacturer’s published data.
- Minimum pickup voltage of the trip and close coils shall conform to the manufacturer’s
published data. In the absence of the manufacturer’s published data, refer to Table 100.20.
- Auxiliary features shall operate in accordance with manufacturer’s published data.
- Protective devices shall operate the breaker per system design.
- Power-factor or dissipation-factor values shall be compared to manufacturer’s published data.
In the absence of manufacturer’s published data the comparison shall be made to similar
breakers.
- Power-factor or dissipation-factor and capacitance values shall be within ten percent of
nameplate rating for bushings. Hot collar tests are evaluated on a milliampere/milliwatt loss
basis, and the results should be compared to values of similar bushings.
- Evaluate each vacuum interrupter in accordance with test equipment manufacturer’s
instructions.
- If no evidence of distress or insulation failure is observed by the end of the total time of
voltage application during the dielectric withstand test, the test specimen is considered to
have passed the test.
- Heaters shall be operational.
- Results of instrument transformer tests shall be in accordance with Section 7.10.
NETA ATS
7.6.2 Circuit
Breakers, Oil, Medium- and High-Voltage
A. Visual and Mechanical
Inspection:
- Compare equipment nameplate data with drawings and specifications.
- Inspect physical and mechanical condition.
- Inspect anchorage, alignment, grounding, and required clearances.
- Verify that all maintenance devices such as special tools and gauges specified by the
manufacturer are available for servicing and operating the breaker.
- Verify correct oil level in all tanks and bushings.
- Verify that breather vents are clear.
- Verify the unit is clean.
- Inspect hydraulic system and air compressor in accordance with manufacturer’s published
data.
- Test alarms and pressure-limit switches for pneumatic and hydraulic operators as
recommended by the manufacturer.
- Perform mechanical operation tests on the operating mechanism in accordance with
manufacturer’s published data.
- While performing internal inspection:
- Remove oil. Lower tanks or remove manhole covers as necessary. Inspect bottom of
tank for broken parts and debris.
- Inspect lift rod and toggle assemblies, contacts, interrupters, bumpers, dashpots,
bushing current transformers, tank liners, and gaskets.
- Verify that contact sequence is in accordance with manufacturer’s published data. In
the absence of manufacturer’s published data, refer to ANSI/IEEE C37.04.
- Fill tank(s) with filtered oil.
- Inspect bolted electrical connections for high resistance using one or more of the following
methods:
- Use of low-resistance ohmmeter in accordance with Section 7.6.2.B.1.
- Verify tightness of accessible bolted electrical connections by calibrated torquewrench
method in accordance with manufacturer’s published data or Table 100.12.
- Perform thermographic survey in accordance with Section 9.
- Verify cell fit and element alignment, if applicable.
- Verify racking mechanism operation, if applicable.
- Perform contact-timing test.
- Perform mechanism-motion analysis.
- *Perform trip/close coil current signature analysis.
- Verify appropriate lubrication on moving current-carrying parts and on moving and sliding
surfaces.
- Record as-found and as-left operation counter readings.
B. Electrical Tests:
- Perform resistance measurements through bolted connections with a low-resistance
ohmmeter, if applicable, in accordance with Section 7.6.2.A.12.1
- Perform insulation-resistance tests for one minute on each pole, phase-to-phase and phase-toground
with circuit-breaker closed, and across each open pole. Test voltage shall be in
accordance with manufacturer’s published data. In the absence of manufacturer’s published
data, use Table 100.1.
- Perform a static contact/pole resistance test.
- *Perform a dynamic contact/pole resistance test.
- *Perform insulation-resistance tests on all control wiring with respect to ground. Applied
potential shall be 500 volts dc for 300-volt rated cable and 1000 volts dc for 600-volt rated
cable. Test duration shall be one minute. For units with solid-state components, follow
manufacturer’s recommendation.
- Remove a sample of insulating liquid in accordance with ASTM D 923. Sample shall be
tested in accordance with the referenced standard.
- Dielectric breakdown voltage: ASTM D 877
- Color: ANSI/ASTM D 1500
- Power factor: ASTM D 924
- Interfacial tension: ASTM D 971
- Visual condition: ASTM D 1524
- Neutralization number (acidity): ASTM D974
- Water content: ASTM D1533
- Perform minimum pickup voltage tests on trip and close coils in accordance with
manufacturer’s published data.
- Verify correct operation of any auxiliary features such as electrical close and trip operation,
trip-free, antipump function.
- Trip circuit breaker by operation of each protective device. Reset all trip logs and indicators.
- Perform power-factor or dissipation-factor tests on each pole with breaker open and each
phase with breaker closed. Determine tank loss index.
- Perform power-factor or dissipation-factor tests on each bushing equipped with a powerfactor/
capacitance tap. In the absence of a power-factor/ capacitance tap, perform hot-collar
tests. These tests shall be in accordance with the test equipment manufacturer’s published
data.
- *Perform a dielectric withstand voltage test in accordance with manufacturer’s published data.
- Verify operation of heaters.
- Test instrument transformers in accordance with Section 7.10.
C. Test Values – Visual and
Mechanical
- Settings for alarm, pressure, and limit switches shall be in accordance with owner’s
specifications. In the absence of owner’s specifications use manufacturer’s published data.
(7.6.2.A.9)
- Compare bolted connection resistance values to values of similar connections. Investigate
values which deviate from those of similar bolted connections by more than 50 percent of the
lowest value. (7.6.2.A.12.1)
- Bolt-torque levels shall be in accordance with manufacturer’s published data. In the absence
of manufacturer’s published data, use Table 100.12. (7.6.2.A.12.2)
- Results of the thermographic survey shall be in accordance with Section 9. (7.6.2.A.12.3)
- Contact timing values shall be in accordance with manufacturer’s published data.
(7.6.2.A.15).
- Travel and velocity values shall be in accordance with manufacturer’s published data.
(7.6.2.A.16)
- Trip/close coil current values shall be in accordance with manufacturer’s published data.
(7.6.2.A.17).
- Operations counter shall advance one digit per close-open cycle. (7.6.2.A.19)
D. Test Values – Electrical
- Compare bolted connection resistance values to values of similar connections. Investigate
values which deviate from those of similar bolted connections by more than 50 percent of the
lowest value.
- Insulation-resistance values of circuit breakers shall be in accordance with manufacturer’s
published data. In the absence of manufacturer’s published data, use Table 100.1. Values of
insulation resistance less than this table or manufacturer’s recommendations should be
investigated.
- Microhm or dc millivolt drop values shall not exceed the high levels of the normal range as
indicated in the manufacturer’s published data. If manufacturer’s published data is not
available, investigate values that deviate from adjacent poles or similar breakers by more than
50 percent of the lowest value.
- Dynamic contact resistance values shall be in accordance with manufacturer’s published data.
- Insulation-resistance values of control wiring shall not be less than two megohms.
- Insulating liquid test results shall be in accordance with Table 100.4.
- Minimum pickup voltage of the trip and close coils shall conform to the manufacturer’s
published data. In the absence of the manufacturer’s published data, refer to Table 100.20.
- Auxiliary features shall operate in accordance with manufacturer’s published data.
- Protective devices shall operate the breaker per system design.
- Power-factor or dissipation-factor values and tank loss index shall be compared to
manufacturer’s published data. In the absence of manufacturer’s published data, the
comparison shall be made to test data from similar breakers or data from test equipment
manufacturers.
- Power-factor or dissipation-factor and capacitance values shall be within ten percent of
nameplate rating for bushings. Hot collar tests are evaluated on a milliampere/milliwatt loss
basis, and the results should be compared to values of similar bushings.
- If no evidence of distress or insulation failure is observed by the end of the total time of
voltage application during the dielectric withstand test, the test specimen is considered to
have passed the test.
- Heaters shall be operational.
- Results of electrical tests on instrument transformers shall be in accordance with Section
7.10.
NETA ATS
7.6.4 Circuit
Breakers, SF6
A. Visual and Mechanical
Inspection:
- Compare equipment nameplate data with drawings and specifications.
- Inspect physical and mechanical condition.
- Inspect anchorage, alignment, and grounding.
- Verify that all maintenance devices such as special tools and gauges specified by the
manufacturer are available for servicing and operating the breaker.
- Verify the unit is clean.
- When provisions are made for sampling, remove a sample of SF6 gas and test in accordance
with Table 100.13. Do not break seal or distort “sealed-for-life” interrupters.
- Inspect operating mechanism and/or hydraulic or pneumatic system and SF6 gas-insulated
system in accordance with manufacturer’s published data.
- Test for SF6 gas leaks in accordance with manufacturer’s published data.
- Verify correct operation of alarms and pressure-limit switches for pneumatic, hydraulic, and
SF6 gas pressure in accordance with manufacturer’s published data.
- If recommended by manufacturer, slow close/open breaker and check for binding, friction,
contact alignment, and penetration. Verify that contact sequence is in accordance with
manufacturer’s published data. In the absence of manufacturer’s published data, refer to
ANSI/IEEE C37.04.
- Perform all mechanical operation tests on the operating mechanism in accordance with the
manufacturer’s published data.
- Inspect all bolted electrical connections for high resistance using one or more of the
following methods:
- Use of a low-resistance ohmmeter in accordance with Section 7.6.4.B.1.
- Verify tightness of accessible bolted electrical connections by calibrated torquewrench
method in accordance with manufacturer’s published data or Table 100.12.
- Perform a thermographic survey in accordance with Section 9.
- Verify the appropriate lubrication on moving current-carrying parts and on moving and
sliding surfaces.
- Perform contact-timing test.
- *Perform trip/close coil signature analysis.
- Perform mechanism motion analysis.
- Record as-found and as-left operation counter readings.
B. Electrical Tests:
- Perform resistance measurements through all bolted connections with a low-resistance
ohmmeter, if applicable, in accordance with Section 7.6.4.A.12.1.
- Perform insulation-resistance tests in accordance with Table 100.1 from each pole-to-ground
with breaker closed and across open poles at each phase. For single-tank breakers, perform
insulation resistance tests in accordance with Table 100.1 from pole-to-pole.
- Perform a contact/pole-resistance test.
- *Perform insulation-resistance tests on all control wiring with respect to ground. Applied
potential shall be 500 volts dc for 300-volt rated cable and 1000 volts dc for 600-volt rated
cable. Test duration shall be one minute. For units with solid-state components or for control
devices that cannot tolerate the voltage, follow manufacturer’s recommendation.
- Perform minimum pickup voltage tests on trip and close coils in accordance with
manufacturer’s published data.
- Verify correct operation of any auxiliary features such as electrical close and trip operation,
trip-free, and antipump function. Reset all trip logs and indicators.
- Trip circuit breaker by operation of each protective device.
- Perform power-factor or dissipation-factor tests on each pole with the breaker open and on
each phase with the breaker closed.
- Perform power-factor or dissipation-factor tests on each bushing equipped with a powerfactor/
capacitance tap. In the absence of a power-factor/ capacitance tap, perform hot-collar
tests. These tests shall be in accordance with the test equipment manufacturer’s published
data.
- *Perform a dielectric withstand voltage test in accordance with manufacturer’s published data.
- Verify operation of heaters.
- Test instrument transformers in accordance with Section 7.10.
C. Test Values – Visual and
Mechanical
-
- SF6 gas shall have values in accordance with Table 100.13. (7.6.4.A.6)
- Results of the SF6 gas leak test shall confirm that no SF6 gas leak exists. (7.6.4.A.8)
- Settings for alarm, pressure, and limit switches shall be in accordance with manufacturer’s
published data. (7.6.4.A.9)
- Compare bolted connection resistance values to values of similar connections. Investigate
values which deviate from those of similar bolted connections by more than 50 percent of the
lowest value. (7.6.4.A.12.1)
- Bolt-torque levels shall be in accordance with manufacturer’s published data. In the absence
of manufacturer’s published data, use Table 100.12. (7.6.4.A.12.2)
- Results of the thermographic survey shall be in accordance with Section 9. (7.6.4.A.12.3)
- Contact timing values shall be in accordance with manufacturer’s published data.
(7.6.4.A.14)
- Trip/close coil current values shall be in accordance with manufacturer’s published data
(7.6.4.A.15)
- Travel and velocity values shall be in accordance with manufacturer’s published data.
(7.6.4.A.16)
- Operations counter shall advance one digit per close-open cycle. (7.6.4.A.17)
D. Test Values – Electrical
-
- Compare bolted connection resistance values to values of similar connections. Investigate
values which deviate from those of similar bolted connections by more than 50 percent of the
lowest value.
- Insulation-resistance values of circuit breakers shall be in accordance with manufacturer’s
published data. In the absence of manufacturer’s published data, use Table 100.1. Values of
insulation resistance less than this table or manufacturer’s recommendations should be
investigated.
- Microhm or dc millivolt drop values shall not exceed the high levels of the normal range as
indicated in the manufacturer’s published data. In the absence of manufacturer’s published
data, investigate values that deviate from adjacent poles or similar breakers by more than 50
percent of the lowest value.
- Insulation-resistance values of control wiring shall not be less than two megohms.
- Minimum pickup voltage of the trip and close coils shall conform to the manufacturer’s
published data. In the absence of the manufacturer’s published data, refer to Table 100.20.
- Auxiliary features shall operate in accordance with manufacturer’s published data.
- Protective devices shall operate the breaker per the system design.
- Power-factor or dissipation-factor values shall be compared to manufacturer’s published data.
In the absence of manufacturer’s published data, the comparison shall be made to test data
from similar breakers or data from test equipment manufacturers.
- Power-factor or dissipation-factor and capacitance test values shall be within ten percent of
nameplate rating for bushings. Hot collar tests are evaluated on a milliampere/milliwatt loss
basis, and the results shall be compared to values of similar bushings.
- If no evidence of distress or insulation failure is observed by the end of the total time of
voltage application during the dielectric withstand test, the test specimen is considered to
have passed the test.
- Heaters shall be operational.
- Results of electrical tests on instrument transformers shall be in accordance with Section
7.10.
NETA ATS
7.6.1.3 Circuit
Breakers, Air, Medium-Voltage
A. Visual and Mechanical
Inspection:
- Compare equipment nameplate data with drawings and specifications
- Inspect physical and mechanical condition.
- Inspect anchorage, alignment, and grounding.
- Verify that all maintenance devices are available for servicing and operating the breaker.
- Verify the unit is clean.
- Verify the arc chutes are intact.
- Inspect moving and stationary contacts for condition and alignment.
- If recommended by manufacturer, slow close/open breaker and check for binding, friction,
contact alignment, and penetration. Verify that contact sequence is in accordance with
manufacturer’s published data. In the absence of manufacturer’s published data, refer to
ANSI/IEEE C37.04.
- Perform all mechanical operation tests on the operating mechanism in accordance with
manufacturer’s published data.
- Inspect bolted electrical connections for high resistance using one or more of the following
methods:
- Use of a low-resistance ohmmeter in accordance with Section 7.6.1.3.B.1.
- Verify tightness of accessible bolted electrical connections by calibrated torquewrench
method in accordance with manufacturer’s published data or Table 100.12.
- Perform a thermographic survey in accordance with Section 9.
- verify cell fit and element alignment.
- Verify racking mechanism operation.
- Inspect puffer operation.
- Verify appropriate lubrication on moving current-carrying parts and on moving and sliding
surfaces.
- Perform contact-timing test.
- *Perform mechanism-motion analysis.
- *Perform trip/close coil current signature analysis.
- Record as-found and as-left operation-counter readings.
B. Electrical Tests:
- Perform resistance measurements through bolted connections with a low-resistance
ohmmeter, if applicable. See Section 7.6.1.3.A.10.1.
- Perform insulation-resistance tests for one minute on each pole, phase-to-phase and phase-toground
with circuit breaker closed, and across each open pole. Apply voltage in accordance
with manufacturer’s published data. In the absence of manufacturer’s published data, use
Table 100.1.
- Perform a contact/pole-resistance test.
- *Perform insulation-resistance tests on all control wiring with respect to ground. Applied
potential shall be 500 volts dc for 300-volt rated cable and 1000 volts dc for 600-volt rated
cable. Test duration shall be one minute. For units with solid-state components or control
devices that can not tolerate the applied voltage, follow manufacturer’s recommendation.
- With breaker in the test position, make the following tests:
- Trip and close breaker with the control switch.
- Trip breaker by operating each of its protective relays.
- Verify mechanism charge, trip-free, and antipump functions.
- Perform minimum pickup voltage tests on trip and close coils in accordance with
manufacturer’s published data.
- *Perform power-factor or dissipation-factor tests with breaker in both the open and closed
positions.
- *Perform power-factor or dissipation-factor tests on each bushing equipped with a powerfactor/
capacitance tap. In the absence of a power-factor/ capacitance tap, perform hot-collar
tests. These tests shall be in accordance with the test equipment manufacturer’s published
data.
- Perform a dielectric withstand voltage test on each phase with the circuit breaker closed and
the poles not under test grounded. Apply voltage in accordance with manufacturer’s
published data. In the absence of manufacturer’s published data, use Table 100.19.
- Measure blowout coil circuit resistance.
- Verify operation of heaters.
- Test instrument transformers in accordance with Section 7.10.
C. Test Values – Visual and
Mechanical
- Mechanical operation and contact alignment shall be in accordance with manufacturer’s
published data. (7.6.1.3.A.9)
- Compare bolted connection resistance values to values of similar connections. Investigate
values which deviate from those of similar bolted connections by more than 50 percent of the
lowest value. (7.6.1.3.A.10.1)
- Bolt-torque levels shall be in accordance with manufacturer’s published data. In the absence
of manufacturer’s published data, use Table 100.12. (7.6.1.3.A.10.2)
- Results of the thermographic survey shall be in accordance with Section 9. (7.6.1.3.A.10.3)
- Contact timing values shall be in accordance with manufacturer’s published data.
(7.6.1.3.A.15).
- Travel and velocity values shall be in accordance with manufacturer’s published data.
(7.6.1.3.A.16)
- Trip/close coil current values shall be in accordance with manufacturer’s published data.
(7.6.1.3.A.17).
- Operations counter shall advance one digit per close-open cycle. (7.6.1.3.A.18)
D. Test Values – Electrical
- Compare bolted connection resistance values to values of similar connections. Investigate
values which deviate from those of similar bolted connections by more than 50 percent of the
lowest value.
- Insulation-resistance values of circuit breakers shall be in accordance with manufacturer’s
published data. In the absence of manufacturer’s published data, use Table 100.1. Values of
insulation resistance less than this table or manufacturer’s recommendations should be
investigated.
- Microhm or dc millivolt drop values shall not exceed the high levels of the normal range as
indicated in the manufacturer’s published data. In the absence of manufacturer’s published
data, investigate values that deviate from adjacent poles or similar breakers by more than 50
percent of the lowest value.
- Insulation-resistance values of control wiring shall not be less than two megohms.
- Breaker mechanism charge, close, open, trip, trip-free, and antipump features shall function
as designed.
- Minimum pickup voltage of the trip and close coils shall conform to the manufacturer’s
published data. In the absence of the manufacturer’s published data, refer to Table 100.20.
- Power-factor or dissipation-factor values shall be compared with previous test results of
similar breakers or manufacturer’s published data.
- Power-factor or dissipation-factor and capacitance values shall be within ten percent of
nameplate rating for bushings. Hot collar tests are evaluated on a milliampere/milliwatt loss
basis, and the results shall be compared to values of similar bushings.
- If no evidence of distress or insulation failure is observed by the end of the total time of
voltage application during the dielectric withstand test, the circuit breaker is considered to
have passed the test.
- The blowout coil circuit shall exhibit continuity.
- Heaters shall be operational.
- The results of instrument transformer tests shall be in accordance with Section 7.10.
NETA ATS
7.6.3 Circuit
Breakers, Vacuum, Medium-Voltage
A. Visual and Mechanical
Inspection:
- Compare equipment nameplate data with drawings and specifications.
- Inspect physical and mechanical condition.
- Inspect anchorage, alignment, and grounding.
- Verify that all maintenance devices such as special tools and gauges specified by the
manufacturer are available for servicing and operating the breaker.
- Verify the unit is clean.
- Perform all mechanical operation tests on the operating mechanism in accordance with
manufacturer’s published data.
- Measure critical distances such as contact gap as recommended by manufacturer.
- Inspect bolted electrical connections for high resistance using one or more of the following
methods:
- Use of low-resistance ohmmeter in accordance with Section 7.6.3.B.1.
- Verify tightness of accessible bolted electrical connections by calibrated torquewrench
method in accordance with manufacturer’s published data or Table 100.12.
- Perform thermographic survey in accordance with Section 9.
- Verify cell fit and element alignment.
- Verify racking mechanism operation.
- Verify appropriate lubrication on moving, current-carrying parts and on moving and sliding
surfaces.
- Perform contact-timing test.
- *Perform trip/close coil current signature analysis.
- *Perform mechanism motion analysis.
- Record as-found and as-left operation counter readings.
B. Electrical Tests:
- Perform resistance measurements through bolted connections with a low-resistance
ohmmeter, if applicable, in accordance with Section 7.6.3.A.8.1.
- Perform insulation-resistance tests for one minute on each pole, phase-to-phase and phase-toground
with the circuit breaker closed, and across each open pole. Test voltage shall be in
accordance with manufacturer’s published data. In the absence of manufacturer’s published
data, use Table 100.1.
- *Perform insulation-resistance tests on all control wiring with respect to ground. Applied
potential shall be 500 volts dc for 300-volt rated cable and 1000 volts dc for 600-volt rated
cable. Test duration shall be one minute. For units with solid-state components, follow
manufacturer’s recommendation.
- *Perform dynamic contact/pole resistance test.
- Perform minimum pickup voltage tests on trip and close coils in accordance with
manufacturer’s published data.
- Verify correct operation of any auxiliary features such as electrical close and trip operation,
trip-free, and antipump function.
- Trip circuit breaker by operation of each protective device. Reset all trip logs and indicators.
- *Perform power-factor or dissipation-factor tests on each pole with the breaker open and each
phase with the breaker closed.
- *Perform power-factor or dissipation-factor tests on each bushing equipped with a powerfactor/
capacitance tap. In the absence of a power-factor/ capacitance tap, perform hot-collar
tests. These tests shall be in accordance with the test equipment manufacturer’s published
data.
- *Perform magnetron atmospheric condition (MAC) test on each vacuum interrupter.
- Perform vacuum bottle integrity (dielectric withstand voltage) test across each vacuum bottle
with the breaker in the open position in strict accordance with manufacturer’s published data.
- Perform a dielectric withstand voltage test in accordance with manufacturer’s published data.
- Verify operation of heaters.
- Test instrument transformers in accordance with Section 7.10.
C. Test Values – Visual and
Mechanical
- Critical distance measurements such as contact gap shall be in accordance with the
manufacturer’s published data. (7.6.3.A.7)
- Compare bolted connection resistance values to values of similar connections. Investigate
values which deviate from those of similar bolted connections by more than 50 percent of the
lowest value. (7.6.3.A.8.1)
- Bolt-torque levels shall be in accordance with manufacturer’s published data. In the absence
of manufacturer’s published data, use Table 100.12. (7.6.3.A.8.2)
- Results of the thermographic survey shall be in accordance with Section 9. (7.6.3.A.8.3)
- Contact timing values shall be in accordance with manufacturer’s published data.
(7.6.3.A.12)
- Trip/close coil current values shall be in accordance with manufacturer’s published data.
(7.6.3.A.13)
- Travel and velocity values shall be in accordance with manufacturer’s published data.
(7.6.3.A.14)
- Operation counter shall advance one digit per close-open cycle. (7.6.3.A.15)
-
D. Test Values – Electrical
<
- Compare bolted connection resistance values to values of similar connections. Investigate
values which deviate from those of similar bolted connections by more than 50 percent of the
lowest value.
- Insulation-resistance values of circuit breakers shall be in accordance with manufacturer’s
published data. In the absence of manufacturer’s published data, use Table 100.1. Values of
insulation resistance less than this table or manufacturer’s recommendations should be
investigated.
- Insulation-resistance values of control wiring shall not be less than two megohms.
- Microhm or dc millivolt drop values shall not exceed the high levels of the normal range as
indicated in the manufacturer’s published data. In the absence of manufacturer’s published
data, investigate values that deviate from adjacent poles or similar breakers by more than 50
percent of the lowest value.
- Dynamic contact resistance values shall be in accordance with manufacturer’s published data.
- Minimum pickup voltage of the trip and close coils shall conform to the manufacturer’s
published data. In the absence of the manufacturer’s published data, refer to Table 100.20.
- Auxiliary features shall operate in accordance with manufacturer’s published data.
- Protective devices shall operate the breaker per system design.
- Power-factor or dissipation-factor values shall be compared to manufacturer’s published data.
In the absence of manufacturer’s published data the comparison shall be made to similar
breakers.
- Power-factor or dissipation-factor and capacitance values shall be within ten percent of
nameplate rating for bushings. Hot collar tests are evaluated on a milliampere/milliwatt loss
basis, and the results should be compared to values of similar bushings.
- Evaluate each vacuum interrupter in accordance with test equipment manufacturer’s
instructions.
- If no evidence of distress or insulation failure is observed by the end of the total time of
voltage application during the dielectric withstand test, the test specimen is considered to
have passed the test.
- Heaters shall be operational.
- Results of instrument transformer tests shall be in accordance with Section 7.10.
NETA ATS
7.6.2 Circuit
Breakers, Oil, Medium- and High-Voltage
A. Visual and Mechanical
Inspection:
- Compare equipment nameplate data with drawings and specifications.
- Inspect physical and mechanical condition.
- Inspect anchorage, alignment, grounding, and required clearances.
- Verify that all maintenance devices such as special tools and gauges specified by the
manufacturer are available for servicing and operating the breaker.
- Verify correct oil level in all tanks and bushings.
- Verify that breather vents are clear.
- Verify the unit is clean.
- Inspect hydraulic system and air compressor in accordance with manufacturer’s published
data.
- Test alarms and pressure-limit switches for pneumatic and hydraulic operators as
recommended by the manufacturer.
- Perform mechanical operation tests on the operating mechanism in accordance with
manufacturer’s published data.
- While performing internal inspection:
- Remove oil. Lower tanks or remove manhole covers as necessary. Inspect bottom of
tank for broken parts and debris.
- Inspect lift rod and toggle assemblies, contacts, interrupters, bumpers, dashpots,
bushing current transformers, tank liners, and gaskets.
- Verify that contact sequence is in accordance with manufacturer’s published data. In
the absence of manufacturer’s published data, refer to ANSI/IEEE C37.04.
- Fill tank(s) with filtered oil.
- Inspect bolted electrical connections for high resistance using one or more of the following
methods:
- Use of low-resistance ohmmeter in accordance with Section 7.6.2.B.1.
- Verify tightness of accessible bolted electrical connections by calibrated torquewrench
method in accordance with manufacturer’s published data or Table 100.12.
- Perform thermographic survey in accordance with Section 9.
- Verify cell fit and element alignment, if applicable.
- Verify racking mechanism operation, if applicable.
- Perform contact-timing test.
- Perform mechanism-motion analysis.
- *Perform trip/close coil current signature analysis.
- Verify appropriate lubrication on moving current-carrying parts and on moving and sliding
surfaces.
- Record as-found and as-left operation counter readings.
B. Electrical Tests:
- Perform resistance measurements through bolted connections with a low-resistance
ohmmeter, if applicable, in accordance with Section 7.6.2.A.12.1
- Perform insulation-resistance tests for one minute on each pole, phase-to-phase and phase-toground
with circuit-breaker closed, and across each open pole. Test voltage shall be in
accordance with manufacturer’s published data. In the absence of manufacturer’s published
data, use Table 100.1.
- Perform a static contact/pole resistance test.
- *Perform a dynamic contact/pole resistance test.
- *Perform insulation-resistance tests on all control wiring with respect to ground. Applied
potential shall be 500 volts dc for 300-volt rated cable and 1000 volts dc for 600-volt rated
cable. Test duration shall be one minute. For units with solid-state components, follow
manufacturer’s recommendation.
- Remove a sample of insulating liquid in accordance with ASTM D 923. Sample shall be
tested in accordance with the referenced standard.
- Dielectric breakdown voltage: ASTM D 877
- Color: ANSI/ASTM D 1500
- Power factor: ASTM D 924
- Interfacial tension: ASTM D 971
- Visual condition: ASTM D 1524
- Neutralization number (acidity): ASTM D974
- Water content: ASTM D1533
- Perform minimum pickup voltage tests on trip and close coils in accordance with
manufacturer’s published data.
- Verify correct operation of any auxiliary features such as electrical close and trip operation,
trip-free, antipump function.
- Trip circuit breaker by operation of each protective device. Reset all trip logs and indicators.
- Perform power-factor or dissipation-factor tests on each pole with breaker open and each
phase with breaker closed. Determine tank loss index.
- Perform power-factor or dissipation-factor tests on each bushing equipped with a powerfactor/
capacitance tap. In the absence of a power-factor/ capacitance tap, perform hot-collar
tests. These tests shall be in accordance with the test equipment manufacturer’s published
data.
- *Perform a dielectric withstand voltage test in accordance with manufacturer’s published data.
- Verify operation of heaters.
- Test instrument transformers in accordance with Section 7.10.
C. Test Values – Visual and
Mechanical
- Settings for alarm, pressure, and limit switches shall be in accordance with owner’s
specifications. In the absence of owner’s specifications use manufacturer’s published data.
(7.6.2.A.9)
- Compare bolted connection resistance values to values of similar connections. Investigate
values which deviate from those of similar bolted connections by more than 50 percent of the
lowest value. (7.6.2.A.12.1)
- Bolt-torque levels shall be in accordance with manufacturer’s published data. In the absence
of manufacturer’s published data, use Table 100.12. (7.6.2.A.12.2)
- Results of the thermographic survey shall be in accordance with Section 9. (7.6.2.A.12.3)
- Contact timing values shall be in accordance with manufacturer’s published data.
(7.6.2.A.15).
- Travel and velocity values shall be in accordance with manufacturer’s published data.
(7.6.2.A.16)
- Trip/close coil current values shall be in accordance with manufacturer’s published data.
(7.6.2.A.17).
- Operations counter shall advance one digit per close-open cycle. (7.6.2.A.19)
D. Test Values – Electrical
- Compare bolted connection resistance values to values of similar connections. Investigate
values which deviate from those of similar bolted connections by more than 50 percent of the
lowest value.
- Insulation-resistance values of circuit breakers shall be in accordance with manufacturer’s
published data. In the absence of manufacturer’s published data, use Table 100.1. Values of
insulation resistance less than this table or manufacturer’s recommendations should be
investigated.
- Microhm or dc millivolt drop values shall not exceed the high levels of the normal range as
indicated in the manufacturer’s published data. If manufacturer’s published data is not
available, investigate values that deviate from adjacent poles or similar breakers by more than
50 percent of the lowest value.
- Dynamic contact resistance values shall be in accordance with manufacturer’s published data.
- Insulation-resistance values of control wiring shall not be less than two megohms.
- Insulating liquid test results shall be in accordance with Table 100.4.
- Minimum pickup voltage of the trip and close coils shall conform to the manufacturer’s
published data. In the absence of the manufacturer’s published data, refer to Table 100.20.
- Auxiliary features shall operate in accordance with manufacturer’s published data.
- Protective devices shall operate the breaker per system design.
- Power-factor or dissipation-factor values and tank loss index shall be compared to
manufacturer’s published data. In the absence of manufacturer’s published data, the
comparison shall be made to test data from similar breakers or data from test equipment
manufacturers.
- Power-factor or dissipation-factor and capacitance values shall be within ten percent of
nameplate rating for bushings. Hot collar tests are evaluated on a milliampere/milliwatt loss
basis, and the results should be compared to values of similar bushings.
- If no evidence of distress or insulation failure is observed by the end of the total time of
voltage application during the dielectric withstand test, the test specimen is considered to
have passed the test.
- Heaters shall be operational.
- Results of electrical tests on instrument transformers shall be in accordance with Section
7.10.
NETA ATS
7.6.4 Circuit
Breakers, SF6
A. Visual and Mechanical
Inspection:
- Compare equipment nameplate data with drawings and specifications.
- Inspect physical and mechanical condition.
- Inspect anchorage, alignment, and grounding.
- Verify that all maintenance devices such as special tools and gauges specified by the
manufacturer are available for servicing and operating the breaker.
- Verify the unit is clean.
- When provisions are made for sampling, remove a sample of SF6 gas and test in accordance
with Table 100.13. Do not break seal or distort “sealed-for-life” interrupters.
- Inspect operating mechanism and/or hydraulic or pneumatic system and SF6 gas-insulated
system in accordance with manufacturer’s published data.
- Test for SF6 gas leaks in accordance with manufacturer’s published data.
- Verify correct operation of alarms and pressure-limit switches for pneumatic, hydraulic, and
SF6 gas pressure in accordance with manufacturer’s published data.
- If recommended by manufacturer, slow close/open breaker and check for binding, friction,
contact alignment, and penetration. Verify that contact sequence is in accordance with
manufacturer’s published data. In the absence of manufacturer’s published data, refer to
ANSI/IEEE C37.04.
- Perform all mechanical operation tests on the operating mechanism in accordance with the
manufacturer’s published data.
- Inspect all bolted electrical connections for high resistance using one or more of the
following methods:
- Use of a low-resistance ohmmeter in accordance with Section 7.6.4.B.1.
- Verify tightness of accessible bolted electrical connections by calibrated torquewrench
method in accordance with manufacturer’s published data or Table 100.12.
- Perform a thermographic survey in accordance with Section 9.
- Verify the appropriate lubrication on moving current-carrying parts and on moving and
sliding surfaces.
- Perform contact-timing test.
- *Perform trip/close coil signature analysis.
- Perform mechanism motion analysis.
- Record as-found and as-left operation counter readings.
B. Electrical Tests:
- Perform resistance measurements through all bolted connections with a low-resistance
ohmmeter, if applicable, in accordance with Section 7.6.4.A.12.1.
- Perform insulation-resistance tests in accordance with Table 100.1 from each pole-to-ground
with breaker closed and across open poles at each phase. For single-tank breakers, perform
insulation resistance tests in accordance with Table 100.1 from pole-to-pole.
- Perform a contact/pole-resistance test.
- *Perform insulation-resistance tests on all control wiring with respect to ground. Applied
potential shall be 500 volts dc for 300-volt rated cable and 1000 volts dc for 600-volt rated
cable. Test duration shall be one minute. For units with solid-state components or for control
devices that cannot tolerate the voltage, follow manufacturer’s recommendation.
- Perform minimum pickup voltage tests on trip and close coils in accordance with
manufacturer’s published data.
- Verify correct operation of any auxiliary features such as electrical close and trip operation,
trip-free, and antipump function. Reset all trip logs and indicators.
- Trip circuit breaker by operation of each protective device.
- Perform power-factor or dissipation-factor tests on each pole with the breaker open and on
each phase with the breaker closed.
- Perform power-factor or dissipation-factor tests on each bushing equipped with a powerfactor/
capacitance tap. In the absence of a power-factor/ capacitance tap, perform hot-collar
tests. These tests shall be in accordance with the test equipment manufacturer’s published
data.
- *Perform a dielectric withstand voltage test in accordance with manufacturer’s published data.
- Verify operation of heaters.
- Test instrument transformers in accordance with Section 7.10.
C. Test Values – Visual and
Mechanical
-
- SF6 gas shall have values in accordance with Table 100.13. (7.6.4.A.6)
- Results of the SF6 gas leak test shall confirm that no SF6 gas leak exists. (7.6.4.A.8)
- Settings for alarm, pressure, and limit switches shall be in accordance with manufacturer’s
published data. (7.6.4.A.9)
- Compare bolted connection resistance values to values of similar connections. Investigate
values which deviate from those of similar bolted connections by more than 50 percent of the
lowest value. (7.6.4.A.12.1)
- Bolt-torque levels shall be in accordance with manufacturer’s published data. In the absence
of manufacturer’s published data, use Table 100.12. (7.6.4.A.12.2)
- Results of the thermographic survey shall be in accordance with Section 9. (7.6.4.A.12.3)
- Contact timing values shall be in accordance with manufacturer’s published data.
(7.6.4.A.14)
- Trip/close coil current values shall be in accordance with manufacturer’s published data
(7.6.4.A.15)
- Travel and velocity values shall be in accordance with manufacturer’s published data.
(7.6.4.A.16)
- Operations counter shall advance one digit per close-open cycle. (7.6.4.A.17)
D. Test Values – Electrical
-
- Compare bolted connection resistance values to values of similar connections. Investigate
values which deviate from those of similar bolted connections by more than 50 percent of the
lowest value.
- Insulation-resistance values of circuit breakers shall be in accordance with manufacturer’s
published data. In the absence of manufacturer’s published data, use Table 100.1. Values of
insulation resistance less than this table or manufacturer’s recommendations should be
investigated.
- Microhm or dc millivolt drop values shall not exceed the high levels of the normal range as
indicated in the manufacturer’s published data. In the absence of manufacturer’s published
data, investigate values that deviate from adjacent poles or similar breakers by more than 50
percent of the lowest value.
- Insulation-resistance values of control wiring shall not be less than two megohms.
- Minimum pickup voltage of the trip and close coils shall conform to the manufacturer’s
published data. In the absence of the manufacturer’s published data, refer to Table 100.20.
- Auxiliary features shall operate in accordance with manufacturer’s published data.
- Protective devices shall operate the breaker per the system design.
- Power-factor or dissipation-factor values shall be compared to manufacturer’s published data.
In the absence of manufacturer’s published data, the comparison shall be made to test data
from similar breakers or data from test equipment manufacturers.
- Power-factor or dissipation-factor and capacitance test values shall be within ten percent of
nameplate rating for bushings. Hot collar tests are evaluated on a milliampere/milliwatt loss
basis, and the results shall be compared to values of similar bushings.
- If no evidence of distress or insulation failure is observed by the end of the total time of
voltage application during the dielectric withstand test, the test specimen is considered to
have passed the test.
- Heaters shall be operational.
- Results of electrical tests on instrument transformers shall be in accordance with Section
7.10.
NETA ATS
/ MTS
TABLE
100.1
NETA ATS
/ MTS
TABLE
100.7
NETA ATS
/ MTS
TABLE
100.8
NETA ATS
/ MTS
TABLE
100.12
NETA ATS
/ MTS
TABLE
100.20
|